GPP Calculator: Grains Per Pound, Dew Point & Vapor Pressure

    Enter a temperature and relative humidity — grains per pound, dew point, wet-bulb, vapor pressure and enthalpy update as you type. Free, no login.

    GPP Calculator

    Grains Per Pound (GPP)

    64.6

    Dew Point

    55.1°F

    Wet-Bulb

    62.6°F

    Humidity ratio (lb/lb)0.0092
    Humidity ratio (g/kg)9.24
    Wet-bulb62.6°F
    Enthalpy28.11 Btu/lb
    Vapor pressure0.438 inHg
    Vapor pressure (kPa)1.48
    Saturation vapor pressure0.876 inHg
    Absolute humidity10.82 g/m³
    Specific volume13.68 ft³/lb
    Barometric pressure14.70 psia
    Formulas used

    pws = exp(C8/T + C9 + C10·T + C11·T² + C12·T³ + C13·ln T) — ASHRAE Hyland-Wexler, T in °R

    pw = RH ÷ 100 × pws

    W = 0.621945 × pw ÷ (p − pw)

    GPP = W × 7,000

    Dew point: solve pws(Td) = pw numerically

    W = ((1093 − 0.556·Twb)·Ws(Twb) − 0.240·(T − Twb)) ÷ (1093 + 0.444·T − Twb) → solve for Twb

    h = 0.240·T + W·(1061 + 0.444·T) Btu/lb dry air

    p = 14.696 × (1 − 6.8754e−6 × elevation ft)^5.2559 psia

    Compare two readings

    Unaffected / reference air

    60.0 GPP · dew 53.1°F

    Affected area (drying chamber)

    71.8 GPP · dew 58.0°F

    Drying gap

    11.8 GPP

    Temperature difference 15.0°F · enthalpy difference 5.52 Btu/lb

    Last updated:

    What is GPP and why do restorers use it instead of RH?

    GPP — grains per pound — is the actual weight of water vapor carried by one pound of dry air, measured in grains, where 7,000 grains make a pound. A GPP calculator turns two readings your meter already gives you, temperature and relative humidity, into that absolute number. It is also why people search for a gpp humidity chart: they want to see the moisture load, not a percentage that shifts every time the air warms up.

    Relative humidity is a ratio, not a quantity. It tells you how full the air is compared with how much it could hold at that temperature. Heat a room from 70°F to 90°F and the relative humidity falls even though not one drop of water left the building. A technician reading only RH would think the job is drying. The grains stayed exactly where they were.

    GPP does not move when you heat or cool the air. It moves when water evaporates into the air, when outside air leaks in, or when a dehumidifier condenses vapor and pumps it down a drain. That is the whole point: grains change only when moisture actually moves. Every meaningful drying decision — is the dehumidifier producing, is the chamber sealed, is the material still releasing water — is a comparison of grains between two places or two times.

    GPP chart: grains per pound by temperature and relative humidity

    This table is the same calculation as the tool above, laid out so you can see the whole grid at once and sanity check a meter reading without typing anything. Read down to your dry-bulb temperature, across to your relative humidity, and the cell is grains per pound of dry air.

    Grains per pound of dry air by dry-bulb temperature and relative humidity, at sea level pressure
    °F20% RH30% RH40% RH50% RH60% RH70% RH80% RH90% RH
    5010.615.921.226.531.937.342.648.0
    5512.719.125.531.938.444.951.357.8
    6015.222.930.638.346.053.861.669.4
    6518.227.336.545.855.064.373.783.1
    7021.632.543.554.565.576.787.899.1
    7525.638.651.664.677.891.1104.4117.8
    8030.345.661.076.592.1107.8123.7139.6
    8535.653.771.890.2108.7127.3146.1165.1
    9041.863.084.4106.0127.9149.9172.2194.7
    9548.973.898.9124.4150.1176.1202.4229.1
    10057.086.1115.6145.5175.7206.4237.5269.0
    Grains per pound at sea level (14.696 psia). At altitude the same temperature and relative humidity give a higher figure — enter the elevation in the calculator above for the corrected value.

    Two patterns are worth reading off it. Along any row, grains climb steadily with relative humidity — nothing surprising. Down any column, the same relative humidity carries far more water as the air gets warmer: 50% at 90°F holds roughly three times the grains of 50% at 60°F. That is the whole reason a percentage is a poor scoreboard on a drying job.

    For readings between the rows, or for anything above 100°F, below 50°F or at altitude, use the calculator at the top of the page — it takes an elevation input and solves the same equations at any temperature. The psychrometric chart plots the same relationships graphically if you would rather see them as curves.

    How do I calculate GPP from temperature and RH?

    You find the saturation vapor pressure at the air temperature, multiply it by the relative humidity to get the actual vapor pressure, convert that to a humidity ratio, then multiply by 7,000. The calculator above does it instantly, but the steps are worth knowing because they explain why the answer behaves the way it does.

    Take air at 75°F and 60% relative humidity at sea level. Saturation vapor pressure at 75°F is 0.4301 psia. Multiply by 0.60 and the actual vapor pressure is 0.2580 psia. Humidity ratio is 0.621945 × 0.2580 ÷ (14.696 − 0.2580), which gives 0.01112 pounds of water per pound of dry air. Multiply by 7,000 and you have 77.8 grains per pound. Dew point for that same air is 60.2°F and wet-bulb is 65.3°F.

    Two details separate a field-accurate answer from a rough one. The first is the saturation equation: this site uses the ASHRAE Hyland-Wexler formulation rather than a simplified curve fit, and it switches to the over-ice equation below 32°F. The second is barometric pressure. Humidity ratio has pressure in the denominator, so a job at 5,000 feet carries more grains than sea-level air at the same temperature and RH. Enter the elevation and the calculator corrects for it.

    Psychrometric calculator: every value explained

    A psychrometric calculator takes any two properties of moist air and returns all the others, because the state of moist air is fixed once you know two independent values plus the pressure. Here is what each output on this page means on a job.

    • Dry-bulb temperature — what a plain thermometer reads. It drives how fast water can evaporate and how much moisture the air is capable of holding.
    • Relative humidity — the percentage of that capacity currently used. Useful only alongside a temperature.
    • GPP and humidity ratio — the same absolute moisture content in grains per pound and pounds per pound. This is your scoreboard.
    • Dew point — the temperature at which this air starts condensing. Any surface colder than this gets wet.
    • Wet-bulb — the temperature a wetted thermometer settles at as evaporation cools it. The gap between dry-bulb and wet-bulb tells you how thirsty the air is.
    • Vapor pressure — the share of total air pressure exerted by the water vapor itself. Differences in vapor pressure are what actually push moisture out of materials.
    • Enthalpy — total heat content per pound of dry air, sensible plus latent. It explains why a dehumidifier warms the space it dries.
    • Absolute humidity — grams of water per cubic metre, the same idea as GPP expressed per unit volume instead of per unit mass.

    Vapor pressure calculator: what vapor pressure means for drying

    Vapor pressure is the portion of atmospheric pressure produced by water vapor, and drying happens because vapor pressure inside a wet material is higher than vapor pressure in the air around it. Moisture always moves from higher vapor pressure to lower vapor pressure. Nothing else makes a wet floor dry.

    This is why lowering the grains in a room speeds drying: dropping the air's vapor pressure widens the gap between the material and the air, and a wider gap moves water faster. It is also why an unsealed chamber stalls. Outdoor air leaking in raises the room's vapor pressure back up, narrowing the gap, and the material sits there.

    The calculator reports vapor pressure in inches of mercury and kilopascals, plus the saturation vapor pressure at the same temperature. The ratio of those two numbers is relative humidity, which is a neat way to see that RH was never an amount of water in the first place.

    Humidity ratio calculator: humidity ratio vs GPP vs g/kg

    Humidity ratio, GPP and grams per kilogram are three units for one quantity: the mass of water vapor per unit mass of dry air. Humidity ratio is the base figure in pounds of water per pound of dry air, a small decimal like 0.0112. Multiply by 7,000 to get grains per pound. Multiply by 1,000 to get grams per kilogram.

    The conversions are fixed, so one gram per kilogram is exactly seven grains per pound. Restoration in North America runs on grains because the numbers land in a comfortable two-digit range. HVAC engineering and most of the world outside North America use g/kg or the raw ratio. The toggle on the calculator switches between them without changing anything physical.

    Note that all three are per pound or kilogram of dry air, not per pound of the mixture. That convention keeps the denominator constant when moisture is added or removed, which is exactly what makes the number useful for tracking a drying job.

    What is grain depression and what should it be?

    Grain depression is the difference in grains per pound between the air going into a dehumidifier and the air coming out of it. Measure intake temperature and RH, measure exhaust temperature and RH, convert both to GPP, and subtract. The "Dehumidifier intake vs exhaust" preset in the comparison panel above does both conversions and the subtraction for you.

    It is the fastest honest answer to "is this machine actually working?" A unit with a failed compressor, a fouled coil or a stuck defrost cycle still blows warm air and still sounds fine. If the exhaust grains are not meaningfully lower than the intake grains, it is a heater, not a dehumidifier.

    Target figures are not published here. What counts as an acceptable depression depends on the machine type, the intake conditions it is being asked to work in and the manufacturer's performance curve — a reading that is fine at 90 grains intake means something different at 45.

    What is the drying gap?

    The drying gap is the difference in grains per pound between the unaffected reference air and the air inside the drying chamber. Use the "Affected vs unaffected" preset above: enter the reference reading, enter the chamber reading, and the panel returns the gap.

    The gap tells you whether you have built a drying environment at all. If chamber air holds the same grains as the hallway outside it, you have a fan-cooled room, not a chamber. A negative gap — chamber wetter than the reference — is normal at the start of a job while materials release water, and it should close day by day as the equipment removes more than the materials give up.

    Track it over time rather than judging a single reading. Two consecutive days with no movement in the gap usually means something changed: a door propped open, a unit tripped off, or a wet cavity nobody has opened yet. No target value is given here.

    Dew point and secondary damage

    Any surface colder than the air's dew point will collect condensation, which is how a drying job creates new damage in rooms the original water never reached. The classic examples are exterior walls in cold weather, uninsulated ductwork, slab floors, window glass and the cold side of a poorly sealed containment barrier.

    Heating the air makes this worse, not better, if you have not lowered the grains. Warmer air holds more vapor and drives more evaporation, but the dew point stays put — so the extra moisture in the air finds the coldest surface in the building and lands on it. That is why heat and dehumidification belong together.

    Take a surface temperature with an infrared thermometer, compare it with the dew point from this calculator, and act on the difference. The dew point calculator does that comparison directly: enter a surface temperature and it reports how far above or below the dew point it sits.

    Common psychrometric mistakes

    • Judging progress on relative humidity. RH falls whenever the air warms. Convert to grains before you decide anything.
    • Comparing readings taken at different temperatures without converting. Two RH numbers from two rooms at different temperatures are not comparable at all.
    • Taking the reference reading inside the affected building. If the whole structure is wet, an interior hallway is not unaffected air.
    • Never checking the dehumidifier's own output. Intake and exhaust grains take thirty seconds and catch a dead machine on day one instead of day four.
    • Ignoring surface temperatures. Air readings look perfect while a cold exterior wall quietly sweats.
    • Adding air movers without adding dehumidification. More evaporation with the same vapor removal just raises the grains and slows everything down.
    • Using sea-level assumptions at altitude. At elevation the same temperature and RH carry more grains than the chart on the wall says.

    Other free tools

    Psychrometric chart, dehumidifier sizing and ACH

    These three tools have been on this page since it launched and are unchanged. The chart also has its own full-screen version at the psychrometric chart page.

    Interactive Psychrometric Chart

    Dry-bulb temperature & RH plotted live — read GPP, dew point, and saturation off the chart

    Loading chart…

    Need the full version? Open thepsychrometric chart page.

    Frequently asked questions

    A psychrometric chart is a graph that plots all the physical properties of moist air on a single page — dry-bulb temperature, relative humidity, dew point, grains per pound (GPP), and wet-bulb temperature. Knowing any two values lets you find every other property by tracing the chart. Restoration technicians use it to make drying decisions and to verify dehumidifier performance.

    Enter a dry-bulb temperature and relative humidity. The chart plots a dot at that exact air condition. The curved lines are constant relative humidity (10% through 100% saturation). The bottom axis is temperature in °F; the right axis is GPP. Tracing horizontally from your point to the saturation curve gives dew point; the GPP value is shown directly on the right.

    Psychrometry is one of the most technical topics on the IICRC WRT exam. Expect questions involving GPP, dew point, RH changes when heating or cooling air, and dehumidifier performance — all of which are read directly off the chart. Practice with this interactive version until the relationships become reflex.

    What does GPP mean?

    GPP stands for grains per pound: the weight of water vapor carried by one pound of dry air, where 7,000 grains make a pound. It is a measure of absolute humidity, so unlike relative humidity it does not change when the air is heated or cooled. Restorers compare the GPP of the affected area, an unaffected area, the outside air and the dehumidifier exhaust to see whether a drying system is removing water or just moving it.

    How to calculate GPP

    Start with dry-bulb temperature and relative humidity. Look up the saturation vapor pressure for that temperature, multiply it by the relative humidity to get the actual vapor pressure, convert that to a humidity ratio — W = 0.622 × Pv ÷ (P − Pv), where P is atmospheric pressure — and multiply W by 7,000 to get grains per pound. The calculator above runs exactly those steps.

    Worked example: air at 75°F and 50% RH holds about 65 grains per pound, with a dew point near 55°F. Cool that same air to 60°F without removing any water and the relative humidity climbs to about 84% while the GPP stays at 65 — which is why a drying log tracks grains, not RH.

    More about grains per pound

    Grains Per Pound (GPP) is a measure of absolute humidity — the actual weight of water vapor in a pound of dry air. Restoration technicians use GPP instead of relative humidity because it doesn't change with temperature, making it the true indicator of how wet the air is. The IICRC S500 standard relies on GPP to evaluate drying conditions.

    GPP is derived from psychrometric formulas using dry-bulb temperature and relative humidity. The calculator above finds saturation vapor pressure with the ASHRAE Hyland-Wexler equation, multiplies by RH to get actual vapor pressure, then converts the humidity ratio (pounds of water per pound of dry air) into grains per pound (1 lb = 7,000 grains).

    Dew point is the temperature at which air becomes saturated and water vapor condenses into liquid. In restoration, keeping surface temperatures above the dew point prevents secondary damage like condensation on cold walls, windows, or HVAC components. A rising dew point during a job is a red flag that moisture is being added to the air faster than it's being removed.

    Frequently asked questions

    Yes. Every calculator on this site runs in your browser with no login, no email address and no paywall. Nothing you type is sent anywhere, which is why it keeps working on a jobsite with a weak signal once the page has loaded.

    Saturation vapor pressure comes from the ASHRAE Hyland-Wexler equations (over water at or above 32°F, over ice below it). Humidity ratio is W = 0.621945 × pw ÷ (p − pw), and GPP is that ratio multiplied by 7,000 grains per pound. Dew point is found by inverting the saturation equation numerically rather than using the Magnus approximation, and wet-bulb is solved by iteration.

    Humidity ratio depends on barometric pressure, not just temperature and relative humidity. At altitude there is less air pressure, so the same temperature and RH give a slightly higher humidity ratio. Enter the site elevation in feet and the calculator recalculates barometric pressure using the standard-atmosphere formula.

    They measure the same thing — the mass of water vapor carried by a unit mass of dry air — in different units. GPP is grains of water per pound of dry air, used across North American restoration. Grams per kilogram is the metric equivalent. One g/kg equals seven grains per pound, so the toggle on the calculator simply rescales the same number.

    It is a good way to build a feel for how the numbers move, which is what exam questions test. Change the temperature with relative humidity fixed and watch GPP climb; change relative humidity with temperature fixed and watch dew point move. Then take the free practice test and see how those relationships show up in scenario questions.

    Once the page is loaded, yes — the math runs entirely in your browser, so the inputs and results keep working if you lose signal mid-job. Reloading the page needs a connection.

    Try the free 20-question practice test — scenario questions on the topics the WRT exam covers, with an explanation after every answer.